JSB Products › Conventional Detectors
Conventional Detectors Detector Range
Photoelectric smoke detector (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Photoelectric smoke detector (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Opto-heat detector will respond better to fast clean burning fires yet maintain the advantage of optical detectors when detecting smouldering fires. The thermal enhancement of this detector allows a higher alarm threshold which provides a greater rejection of false alarms. The detector will also raise an alarm at temperatures above 135°F.
Rate of Rise detector and Fixed Heat detector will detect a rapid increase in temperature or temperatures above 135°F or 194°F (dependent on switch selection) and should be used in environments where the ambient conditions might cause false alarms if smoke detection were to be used, for example where there is a high level of dust, fumes, steam or smoke under normal conditions.
Features
- Stylish low profile design
- 360º viewable LED design
- Removable detector chamber
- Drift compensation
Benefits
- Plug and play - no hard addressing required
- ‘Clean me’ feature means sensor can be cleaned on site using the JSB manual cleaning procedure
|
Code |
UCPD-2W |
UCPT-2W |
UCHT-2W |
UCHTI-2W |
UCHR-2W |
UCHRI-2W |
|---|---|---|---|---|---|---|
|
Description |
Conventional Detector Optical, 2 Wire |
Conventional Detector Opto-Heat, 2 Wire |
Conventional Detector Fixed Heat, 135ºF, 2 Wire |
Conventional Detector Fixed Heat, 194ºF, 2 Wire |
Conventional Detector Rate of Rise & Fixed Heat 135ºF, 2 Wire |
Conventional Detector Rate of Rise & Fixed Heat 194ºF, 2 Wire |
|
Standards |
UL268 |
UL268 |
UL521 |
UL521 |
UL521 |
UL521 |
|
Supply Ratings |
||||||
|
Working Voltage |
15 V dc to 30 V dc |
15 V dc to 30 V dc |
15 V dc to 30 V dc |
15 V dc to 30 V dc |
15 V dc to 30 V dc |
15 V dc to 30 V dc |
|
Voltage Waveform |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
|
Standby Current |
95 μA (average) |
95 μA (average) |
70 μA (average) |
70 μA (average) |
70 μA (average) |
70 μA (average) |
|
Alarm Current |
must be held externally to 40 mA (max) |
must be held externally to 40 mA (max) |
must be held externally to 40 mA (max) |
must be held externally to 40 mA (max) |
must be held externally to 40 mA (max) |
must be held externally to 40 mA (max) |
|
Surge Current |
340 μA (max) |
340 μA (max) |
340 μA (max) |
340 μA (max) |
340 μA (max) |
340 μA (max) |
|
Timings |
||||||
|
Start-up Time |
20 seconds |
20 seconds |
20 seconds |
20 seconds |
20 seconds |
20 seconds |
|
Reset Time |
2 seconds (max) |
2 seconds (max) |
2 seconds (max) |
2 seconds (max) |
2 seconds (max) |
2 seconds (max) |
|
Sensitivity |
||||||
|
Sensitivity |
2.55+/- 0.33%/ft |
2.55+/- 0.33%/ft |
N/A |
N/A |
N/A |
N/A |
|
Sensitivity Checker |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
|
Heat Class |
||||||
|
Heat Element Rating |
N/A |
135ºF |
135ºF |
194ºF |
135ºF |
194ºF |
|
Heat Detector Spacing |
N/A |
50ft (heat alone operation) |
50ft |
50ft |
50ft |
50ft |
| Mounting Position | Ceiling in open areas | Ceiling in open areas | Ceiling in open areas | Ceiling in open areas | Ceiling in open areas | Ceiling in open areas |
|
Environmental |
||||||
|
Operating Temperature |
32ºF to 100ºF |
32ºF to 100ºF |
32ºF to 100ºF |
32ºF to 150ºF |
32ºF to 150ºF |
32ºF to 150ºF |
|
Mounting Position |
Ceiling in open areas |
Ceiling in open areas |
Ceiling in open areas |
Ceiling in open areas |
Ceiling in open areas |
Ceiling in open areas |
|
Compatibility |
||||||
|
Compatibility Indentifier |
W001 |
W001 |
W001 |
W001 |
W001 |
W001 |
|
Compatible Bases |
CB or CB2E |
CB or CB2E |
CB or CB2E |
CB or CB2E |
CB or CB2E |
CB or CB2E |
|
Suitable for use with |
JSB UL fire systems |
JSB UL fire systems |
JSB UL fire systems |
JSB UL fire systems |
JSB UL fire systems |
JSB UL fire systems |
| Code | Description |
|---|---|
| UCPTR-4W | 4 Wire Detector |
| UCPD-2W | 2 Wire Detector, Optical |
| UCPT-2W | 2 Wire Detector, Opto-Heat |
| UCHT-2W | 2 Wire Detector, Fixed Heat 135°F |
| UCHTI-2W | 2 Wire Detector, Fixed Heat 194°F |
| UCHR-2W | 2 Wire Detector. Rate of Rise and Fixed Heat 135°F |