Menvier Products › DF6100 Range
DF6100 Range Intelligent Addressable Control Panel
The Menvier DF6100 range is available as a high specification 1 or 2 loop intelligent addressable control panel, offering sophisticated functionality with simple end user operation.
Download Menvier DF6100 Range Data Sheet
The Menvier DF6100 range is available as a high specification 1 or 2 loop intelligent addressable control panel, offering sophisticated functionality with simple end user operation.
The simplicity of operation, powerful cause and effect programming capability, and competitive pricing make the system suitable for a wide range of small to medium sized projects.
DF6100 uses soft addressing to minimise installation time and remove the potential for error associated with manual addressing.
These panels can operate as a stand alone panel or as part of a network with the Menvier range of DF6000 panels or other DF6100 panels,(additional network card required).
The DF6100 panel has an integral power supply and is supplied with batteries as standard.
An extensive range of compatible intelligent addressable system ancillaries are available to work with the DF6100 all of which incorporate an integral short circuit isolator to provide maximum protection against short circuits on the loop.
Features
- Large versatile touch screen display
- Competitive single or two loop system
- Spur tolerant soft addressing
- Large selection of compatible ancillaries
- Full network capability
- Integral battery and power supply
- 200 address capacity per loop
- Approved to EN54 Pt13 and EN54 Pt2 and Pt4
Benefits
- Simple end user interface
- Range of compatible ancillaries
- System protocol allows fast and accurate configuration
|
Panel type |
DF6100 |
DF61002 |
|---|---|---|
|
Standards |
|
|
|
Number of loops |
1 |
2 |
|
Addresses per loop |
200 |
|
|
Panel sounder circuits |
2 |
|
|
Class change facility |
Operated by external, normally open, volt free contacts |
|
|
Auxiliary relay |
One set of change over contacts, operated in the event of fire activation |
|
|
Auxiliary fire routing |
Monitored 24V dc, 30 mA (max) |
|
|
Auxiliary fire protection |
Monitored 24V dc, 30 mA (max) |
|
|
Auxiliary fault routing |
Monitored 12V dc, 30 mA (max) |
|
|
Output ports |
RS485 and RS232 (for connection of repeaters etc) |
|
|
Mains input voltage |
230V ac +10% / -15% |
|
|
System operating voltage |
24V dc |
|
|
Batteries |
2 x 12V 7Ah |
|
|
Extended battery option |
|
|
|
Standby duration |
24 hours (dependant on loop loading), 72 hours (for extended battery option) |
|
|
Cable entries |
11 top entry cable knockouts (20mm) plus rear entry cable aperture |
|
|
Environmental rating |
IP30, -5ºC to +40ºC, 75% RH (non condensing) |
|
|
Size WxHxD (mm) |
375x357x50 |
|
|
Weight |
8kg |
|
|
EB Size WxHxD (mm) |
|
|
|
EB Weight |
|
|
|
DF6100 |
Intelligent Addressable 1 Loop Control Panel |
|
DF6100NC |
Intelligent Addressable 1 Loop Control Panel c/w Network Card |
|
DF61002 |
Intelligent Addressable 2 Loop Control Panel |
|
DF61002NC |
Intelligent Addressable 2 Loop Control Panel c/w Network Card |
| DF61NETKIT | Network Kit (retro fit) |