Menvier Products › Addressable Sensors
Addressable Sensors Sensors Range
Photoelectric smoke sensor (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Photoelectric smoke sensor (opto) is suitable for most applications giving the fastest response to slow burning or smouldering fires which give rise to large visible smoke particles.
Opto-heat sensor will respond better to fast clean burning fires yet maintain the advantage of optical sensors when detecting smouldering fires. The thermal enhancement of this sensor allows a higher alarm threshold which provides a greater rejection of false alarms. The sensor will also give an alarm at temperatures above 135°F.
Rate of rise with fixed heat sensor settings will detect a rapid increase in temperature or temperatures above 135°F and should be used in environments where the ambient conditions might cause false alarms if smoke detection were to be used, for example where there is a high level of dust, fumes, steam or smoke under normal conditions.
Fixed heat sensors settings will detect temperatures above 135°F or 194°F and should be used in environments where the ambient conditions might cause false alarms if smoke detection were to be used, for example where there is a high level of dust, fumes, steam or smoke under normal conditions. For photoelectric and opto-heat operation the sensor automatically compensates for gradual increase in the scatter signal due to contamination e.g. dust build up.
Features
- Built-in short circuit isolators
- Stylish low profile design
- 360º viewable LED design
- Removable detector chamber
- Drift compensation
Benefits
- Plug and play - no hard addressing required
- ‘Clean me’ feature means sensor can be cleaned on site using the Menvier manual cleaning procedure
- The programmable heat sensor reduces the number of parts required in the system
|
Code |
ULCAP320 |
ULCAPT340 |
ULCAH330 |
|---|---|---|---|
|
Description |
Addressable Sensor, Optical |
Addressable Sensor, Opto-Heat |
Addressable Sensor, Multi-Mode Heat |
|
Standards |
UL268 |
UL268 |
UL521 |
|
Supply Ratings |
|||
|
Working Voltage |
18 V dc to 30 V dc |
18 V dc to 30 V dc |
18 V dc to 30 V dc |
|
Voltage Waveform |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
Filtered dc +/- 1 V (max), ripple @120Hz |
|
Standby Current |
220 μA (average) |
220 μA (average) |
220 μA (average) |
|
Alarm Current |
5 mA (max) |
5 mA (max) |
5 mA (max) |
|
Timings |
|||
|
Start-up Time |
2 seconds |
2 seconds |
2 seconds |
|
Reset Time |
2 seconds (max) |
2 seconds (max) |
2 seconds (max) |
|
Sensitivity |
|||
|
Sensitivity |
2.55+/- 0.33%/ft |
2.55+/- 0.33%/ft |
N/A |
|
Sensitivity Checker |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
Use No-Climb, TRUTEST, UL Listing 77TL |
|
Heat Class |
|||
|
Heat Element Rating |
N/A |
135ºF |
135ºF ROR + Fixed, + Fixed 135ºF Fixed, 194ºF Fixed |
|
Heat Detector Spacing |
N/A |
50ft (heat alone operation) |
50ft |
|
Mounting Position |
Ceiling in open areas |
Ceiling in open areas |
Ceiling in open areas |
|
Environmental |
|||
|
Operating Temperature |
32ºF to 100ºF |
32ºF to 100ºF |
32ºF to 100ºF / 32ºF to 150ºF (194ºF setting) |
|
Compatibility |
|||
|
Compatibility Indentifier |
W002 |
W002 |
W002 |
|
Compatible Bases |
WBA or UCAB300 |
WBA or UCAB300 |
WBA or UCAB300 |
|
Suitable for use with |
Menvier UL fire systems |
Menvier UL fire systems |
Menvier UL fire systems |
| Code | Description |
|---|---|
| ULCAP320 | Addressable Sensor, Optical |
| ULCAPT340 | Addressable Sensor, Opto Heat |
| ULCAH330 |
Addressable Sensor, Multi-Mode Heat, (Programmable as Rate of Rise 135°F or 194°F) |