Menvier Products › ULDF6000 & ULDF6000RM

ULDF6000 & ULDF6000RM Control Panels

The Menvier ULDF6000 is a high specification intelligent addressable, wall or rack mounted, UL Listed fire system available in various loop configurations. It combines sophisticated functionality with simple operation and aesthetically pleasing design.

Download Technical Documentation
Please login or register for the Cooper Fire Community to download the technical documentation for this product.

The Menvier ULDF6000 is a high specification intelligent addressable, wall or rack mounted, UL Listed fire system available in various loop configurations. It combines sophisticated functionality with simple operation and aesthetically pleasing design.

The control panel has the ability to support complex cause and effect programming and a wide range of user controllable functions make the system ideal for a diverse range of projects from industrial applications through to large multi site commercial developments.

The ULDF6000 uses soft addressing to minimise installation time and remove the potential for error associated with manual addressing.

Each of the system components have been specifically designed to operate as part of a ULDF6000 UL Listed system providing assurance that the panel, the detectors, the interfaces and the ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.

Features

  • Touchscreen Display
  • 2 or 4 Class A Style 7 SLC loops
  • Event History Buffer (9,999 events) with Date/Time stamp
  • 4 Notification appliance circuits (NAC's) outputs
  • 3 programmable general purpose relays
  • Dedicated alarm and trouble relays
  • Short circuit isolators incorporated into each loop
  • Up to 200 addresses per loop
  • Fully monitored network cable up to 126 panels
  • Optional integral printer
  • Alarm Verification
  • PAS (Positive Alarm Sequence)
  • Pre-Signal per Point (NFPA 70, 72 compliant)
  • Remote Alarm, NAC Silenced, Alarm Reset, Trouble, Supervisory and Drill via addressable modules

Benefits

  • Supports a comprehensive range of soft addressing modules and devices for greater flexibility in design
  • Menu driven graphical user interface for ease of operation
  • Reduced commissioning time through soft addressing and auto learn functions
  • Programming and trouble-shooting time minimised by using a range of features such as auto config, walk test, system details, analogue values, etc

Code

ULDF6000 and ULDF6000RM

Description

UL Intelligent Addressable Control Panel

Standards

UL864 9th edition

Primary Operating Supply

120/240 V, 60 Hz, 2.0 A Supervised

Secondary Operating Supply

Battery Voltage
Battery Charge Current
Battery Derating Factor
Battery Capacity Supervised

24 V dc
1.0 A (max)
0.1
12 Ah (max)

Notification Appliance Circuits
Class B, Style Y, Sounder Group 1 sounder 1, Sounder Group 1 sounder 2, Sounder Group 2 sounder 1, Sounder Group 2 sounder 2

Output Voltage

24 V dc

Output Current

0.75 (max)

Line Impedance

50 ohms

 

When the product is powered by 240 V ac, the maximum current of 3.0 A is shared between these circuits.

 

When the product is powered by 120 V ac, the maximum current of 2.25 A is shared between these circuits.

 

Supervised, Power limited, Regulated

Notification Appliance Circuits
Class B, Style Y, SYNC MODULE.  NAC1, NAC2

Output Voltage

24 V dc

Output Current

0.5 A (max)

Line Impedance

50 ohms (max)

 

The maximum current of 0.5 A is shared between these circuits.

 

Supervised, Power limited, Regulated

Alarm, Trouble Contacts. Relay Expansion

Unity Power Factor

30 V dc

 

For connection to power limited sources only

Aux Relay (AC Trouble) Contacts

Unity Power Factor

30 V dc, 1 A

 

For connection to power limited sources only

Signaling Line Circuit Style [7] Class [A] – (Addressable Loop)

Rated Voltage

24 V dc

Maximum Current

500 mA

Line Impedance

50 Ω (max)

 

Supervised, Power limited

Network SLC

 

Voltage

5 V dc

Current

100 mA (max)

Line Impedance

50Ω (max)

 

Power Limited

 

Limited to same-enclosure Installations

Compatibility

Suitable for use with

Menvier UL fire systems

 

Code Description
ULDF60002G 2 Loop Panel
ULDF60004G 4 Loop Panel
ULDF60002GP 2 Loop Panel c/w Integral Printer
ULDF60004GP 4 Loop Panel c/w Integral Printer
ULDF60002GNC 2 Loop Panel c/w Network Card
ULDF60004GNC 4 Loop Panel c/w Network Card
ULDF60002GPNC 2 Loop Panel c/w Integral Printer, Network Card
ULDF60004GPNC 4 Loop Panel c/w Integral Printer, Network Card
ULDF60002RM 2 Loop Panel Red Metal Box
ULDF60004RM 4 Loop Panel Red Metal Box
ULDF60002PRM 2 Loop Panel c/w Integral Printer Red Metal Box
ULDF60004PRM 4 Loop Panel c/w Integral Printer Red Metal Box
ULDF60002NCRM 2 Loop Panel c/w Network Card Red Metal Box
ULDF60004NCRM 4 Loop Panel c/w Network Card Red Metal Box
ULDF60002PNCRM 2 Loop Panel c/w Integral Printer, Network Card Red Metal Box
ULDF60004PNCRM 4 Loop Panel c/w Integral Printer, Network Card Red Metal Box
ULDFR6000L2 Rack mounted 2 Loop Panel
ULDFR6000L4 Rack Mounted 4 Loop Panel
ULDFR6000L2NC Rack Mounted 2 Loop Panel c/w Network Card
ULDFR6000L4NC Rack Mounted 4 Loop Panel c/w Network Card