Menvier Products › ULCSUM355
ULCSUM355 Shop Monitor Unit
An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
The ULCSUM355 shop monitor unit is designed to enable small units with conventional fire detection to be fully integrated with a main analogue addressable fire system. It is ideal for applications such as connecting individual shop units into a main shopping centre system.
An extensive range of interfaces are available to support the Menvier range of UL control panels, providing solutions for most design requirements.
The ULCSUM355 shop monitor unit is designed to enable small units with conventional fire detection to be fully integrated with a main analogue addressable fire system. It is ideal for applications such as connecting individual shop units into a main shopping centre system.
An external power supply is required to drive the 2 conventional sounder circuits. This power supply must be UL1481 listed, regulated for fire and current limited.
Features
- Quick and simple to install
- Accepts a zone of UL approved conventional detectors and callpoints
- Provides 2 conventional sounder circuits
- Only takes a single address
- Includes output changeover relay
- Inputs monitored for open, short circuits and ground trouble
Benefits
- Plug and play - no hard addressing required
- Easy to expand a system using exsiting wiring
- No external short circuit isolator required
|
Code |
ULCSUM355 |
|---|---|
|
Description |
Shop Monitor Unit |
|
Standards |
UL864 9th edition |
|
Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited |
|
|
Voltage |
24 V dc |
|
Current |
4.9 mA to 5.0 mA |
|
Line Impedance |
50 Ω (max) |
|
Detector Zone,Style C, Class B, Supervised, Power Limited |
|
|
Voltage |
21 V dc to 26 V dc, 22.9 V dc (nom) |
|
Current (Alarm) |
17 mA to 40 mA |
|
Line Impedance |
2.5 Ω (max) |
|
End of Line Resistor |
5.6 kΩ |
|
Fire Input Trigger |
680 Ω |
|
|
UPCD-2W, UCPT-2W, UCHRI, UCHT any combination thereof |
|
Compatibility Identifier |
ULCV1 |
|
Sounder 1, Sounder 2, Style Y, Class B, Supervised, Power Limited |
|
|
Voltage |
24 V dc |
|
Current |
1 A (max) |
|
Line Impedance |
8 Ω |
|
End of Line Resistance |
12 kΩ |
|
Callpoint Zone, Style C, Class B, Supervised, Power Limited |
|
|
Voltage(8.4 Vpp pulsed every 1 second) |
8.4 V |
|
Current |
1.2 mA |
|
Line Impedance |
16 Ω |
|
End of Line Resistor |
6.8 kΩ |
|
Trigger Resistor |
680 Ω |
|
24 V external PSU, Supervised, Power Limited |
|
|
Voltage |
24 V dc |
|
Current |
2 A (max) |
|
End of Line Resistor |
12 kΩ |
|
Line Impendance |
4 Ω |
|
Gauge Wire |
12 AWG UL 1481 listed regulated for fire, current limited |
|
Environmental |
|
|
Operating Temperature |
0°C to 49°C |
|
Humidity (Non Condensing) |
0 to 93 %RH |
|
Physical |
|
|
Dimensions (H x W x D) |
180mm x 129mm x 60mm |
|
Weight |
0.28kg |
|
Ingress Protection |
IP65 |
|
Compatibility |
|
|
Suitable for use with |
Menvier analogue addressable fire systems |
| Code | Description |
|---|---|
| ULCSUM355 | Shop Monitor Unit |