The MIU872 is a single zone input, soft addressed, micro interface, incorporating integral short circuit isolators.

It is fully compatible with the current range of Cooper intelligent addressable control panels.

It is suitable for interfacing a zone of up to 20 conventional Cooper detectors onto a Cooper intelligent addressable control panel.

It will operate with any of our current conventional detectors in configuration with a schottky diode type base (CDBB300).

Features

  • Soft addressed
  • Integral short circuit isolator
  • Single address
  • Accepts a zone of up to 20 Cooper conventional detectors
  • Input monitored for open, short circuit and earth
  • contact faults
  • Active end of line monitoring

Benefits

  • Quick and simple to install
  • No hard addressing required (Plug and play)
  • Compact size
  • Easy to expand a system using existing wiring
  • No external power supply required

 

Code

MIU872

Description

Micro Zone Monitor Unit

Standards

EN54 Pt17 & Pt18

Specification

Operating Voltage

18V dc to 30V dc

Quiescent Current

26mA (nom)

Load with 20 Detectors, and

Unlimited Callpoints

3.2 mA (nom)

Alarm Load with 20 Detectors, and

Unlimited Callpoints

8.0mA (nom)

Detector Zone

Detectors per Zone

20 (max)

End of Line Monitor

Active end of line unit – EOLM-1

Fire Input Trigger Resistance

680Ω (nom)

Short Circuit Fault

Threshold Resistance

100Ω (max)

Open Circuit Fault

Threshold Resistance

39KΩ (min)

Environmental

Operating Temperature

-10oC to +60oC

Humidity (Non Condensing)

0 to 95% RH

Physical

Construction

PC/ABS

Dimensions (HxWxD)

65mm x 35mm x 18.5mm

Weight

0.28kg

Ingress Protection

IP40