Products › JSB Bi-Wire Control Panel
JSB Bi-Wire Control Panel
The JSB range of Bi-Wire control panels are designed with Cooper patented 2 wire technology (Patent Number GB2293257) and also includes patented ‘Self-Check’ detector features (Patent Number EP:02253889).
Download JSB Bi-Wire Panel Range Data Sheets
The JSB range of Bi-Wire control panels are designed with Cooper patented 2 wire technology (Patent Number GB2293257) and also includes patented ‘Self-Check’ detector features (Patent Number EP:02253889).
Bi-Wire conventional detectors, sounders, LED beacons, and relay modules, all share the same zone wiring, delivering significant savings in both cable
and installation costs.
All panels in this range have the facility to flash detector LED’s in a zone to facilitate the location of any wiring fault in that zone, thereby simplifying the
fault finding process.
The 4 and 8 zone panels provide enhanced features, which includes HMO programming per zone via the easily accessible DIP switch. If a zone is programmed for HMO and a fire occurs in that zone, only the sounders in that zone will sound, if the fire is cleared within 2 minutes, the panel will reset automatically, otherwise the sounders in all the zones will operate.
Features
- 2, 4, and 8 zone panels
- Self-Check features
- Detectors, sounders and relay modules share same wiring
- Repeater output on 4 and 8 zone panel
- Class change facility
- Selectable fire/fault relay
- Supports up to 20 detectors and 20 sounders / ancillaries per zone
- Detector removal indication
- Maintenance-free poly switch
- Weekly test/walk test facility
Benefits
- Minimise cabling requirements
- Reduced installation time
- Maximises installation savings
- 4 and 8 zone panels ‘HMO’ compliant
- Simplified fault finding process
- Improved system integrity
|
Model |
FX2202BW |
FX2204BWHMO |
FX2208BWHMO |
|---|---|---|---|
|
Standards |
EN54-2: 1998 & EN54-4:1998 EN50130-4: 1996 EN500081-1: 1992 & EN61000-2-2: 1994 |
||
|
Number of zones |
2 |
4 |
8 |
|
Detectors/Sounders per zone |
20-20 |
||
|
Alarm circuit code |
150mA per zone |
|
|
|
End of line devices |
Active end of line monitoring unit |
||
|
Auxiliary fire signal/fault o/p |
1A 24V dc single pole changeover contacts |
||
|
HMO facility |
N/A |
Yes (all zones) |
|
|
Mains input voltage |
230V ac-10% + 15% |
||
|
System operating voltage |
24V dc |
||
|
Satndby Duration |
|
||
|
Battery (sealed lead acid) |
1 x 2.1 Ah 12V |
1 x 3.2 Ah 12V |
2 x 3.2 Ah 12V |
|
Recharge period |
24 Hours |
||
|
Panle construction |
Polycarbonate housing & back box |
||
|
Cable entries |
Top: 12 x 20mm entries with blanking plugs, rear cable entry aperture. |
||
|
Environmental Rating |
IP30. -5˚C to +40˚C Humidity 75% max (non condensing) |
||
|
Dims WxHxD (mm) |
260 x 212 x 72 |
332 x 270 x 92 |
|
|
FX2202BW |
2 Zone Panel |
|
FX2204BWHMO |
4 Zone Panel |
|
FX2208BWHMO |
8 Zone Panel |
Cooper Fire Catalogue
Download and browse the complete Cooper Fire product catalogue