Products › Type B Handset
Type B Handset
This VoCALL Emergency Voice Communication System (EVCS) is designed to fully comply with BS5839 Pt9 2003 (abb. Pt9) for use as a fire telephone system, disabled refuge call system or as a combined system when both fire telephones and disabled refuge points are required. The standard states that where both systems are fitted to a building these should form a single system.
An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters during emergencies in high rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.
The VoCALL type B handset is designed to be versatile, compact and easy to use refuge call point.
This unit can either be surface or flush mounted using a simple to install bezel (CFVCFHB).
Features
- Compact design
- High volume ringer
- Status LED
- 20mm cable glands
- Loop output for hearing impaired users
- Tactile braille signage
- Full duplex operation
- Flush bezel available
- Stainless steel option
Benefits
- Versatility, the unit can beused on all the VoCALL systems
- Full duplex operation, allowing 2 way voice communication
- Tactile braille signage to assist partially sighted people to easily operate refuge point.
| Code | CFVCSHFG | CFVCSHF | CFVCSHFSS |
| Description | Type B Handset, Surface Mount | Type B Handset, Surface Mount | Type B Handset, Surface Mount |
| Standards |
EMC: EN55103-1 & EN55103-2 LVD: EN60950 Product Family BS5839 Pt9 & BS9999 & EN60118-4 |
EMC: EN55103-1 & EN55103-2 LVD: EN60950 Product Family BS5839 Pt9 & BS9999 & EN60118-4 |
EMC: EN55103-1 & EN55103-2 LVD: EN60950 Product Family BS5839 Pt9 & BS9999 & EN60118-4 |
| Outstation Cables | |||
| Grade | Enhanced | Enhanced | Enhanced |
| Cores | 2 core 1mm or 1.5mm | 2 core 1mm or 1.5mm | 2 core 1mm or 1.5mm |
| Distance | 500m | 500m | 500m |
| Indications & Controls | |||
| Status | LEDs 2 off red (ashes location lights, solid in use) | LEDs 2 off red (ashes location lights, solid in use) | LEDs 2 off red (ashes location lights, solid in use) |
| Call | Press to call button | Press to call button | Press to call button |
| Cancel | Press to cancel button | Press to cancel button | Press to cancel button |
| Physical | |||
| Construction | Zintec, Powder Coated | Zintec, Powder Coated | Zintec, Powder Coated |
| Colour Option | Green | Red | Stainless Steel |
| Dimensions (H x W x D) | 133mm x 133mm x 45mm | 133mm x 133mm x 45mm | 133mm x 133mm x 45mm |
| Weight | 1105g | 1105g | 1105g |
|
CFVCSHF |
Type B Handset, Surface Mount (Red) |
|
CFVCSHFG |
Type B Handset, Surface Mount (Green) |
|
CFVCSHFSS |
Type B Handset, Surface Mount (Stainless Steel) |
| CFVCFHB | Flush Mounting Bezel (Stainless Steel) |
Cooper Fire Catalogue
Download and browse the complete Cooper Fire product catalogue