Products › VoCALL 8 Line Exchange Unit
VoCALL 8 Line Exchange Unit
This VoCALL Emergency Voice Communication System (EVCS) is designed to fully comply with BS5839 Pt9 2003 (abb. Pt9) for use as a fire telephone system, disabled refuge call system or as a combined system when both fire telephones and disabled refuge points are required. The standard states that where both systems are fitted to a building these should form a single system.
An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters during emergencies in high rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.
The VoCALL 8 line exchange unit (CFCVX8) is a small wall mounted unit which can be distributed around the site and hidden from view in such places as rises, stairwells and cupboards.
Using this system greatly reduces the cabling requirement and equipment ‘on view ‘ in such key places as reception areas, making the system much more aesthetically pleasing to the customer as well reducing the cost of installation.
Features
- Can control up to 8 independent monitored lines
- Built in monitored 1A charger for 12V SLA batteries
- 12 status LEDs
- Dry contact for fault or “in-use” indication
- Serial port for configuration or updates
- Dual network ports which provide power for the master handsets
- Full duplex system
- Compact design
Benefits
- LED indication, for effective & easy fault finding
- Fault or ‘in-use’ relay, can be connected to a fire panel or BMS
- Global configuration, upload information quickly via a PC using the serial port
- Up to 32 distributed units on any network, no central exchange rack required
|
Physical |
|
|---|---|
|
Height |
296mm |
|
Width |
210mm |
|
Depth |
80mm |
|
Weight |
1600g |
|
Material |
Zintec, Texture powder coated RAL 7032 |
|
Power Supply |
|
|
Voltage |
230V ac ± 20% |
|
Current |
11mA |
|
Battery |
12V SLA 3.2Ah (Not supplied) |
|
Charger |
1A Controlled impedance |
|
Monitoring |
Open, short & high impedance cell |
|
Processing |
|
|
Architecture |
AVR RISK |
|
Clock |
16MHz |
|
Memory |
4K Ram 20K EEProm 128K Flash |
|
Monitoring |
125mS Asynchronous watchdog Checksum on EEPROM & flash |
|
CFVCX8 |
Network 8 Line Exchange Unit |
Cooper Fire Catalogue
Download and browse the complete Cooper Fire product catalogue