Products › VoCALL 8 Line Exchange Unit

VoCALL 8 Line Exchange Unit

This VoCALL Emergency Voice Communication System (EVCS) is designed to fully comply with BS5839 Pt9 2003 (abb. Pt9) for use as a fire telephone system, disabled refuge call system or as a combined system when both fire telephones and disabled refuge points are required. The standard states that where both systems are fitted to a building these should form a single system.

An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters during emergencies in high rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.

Download Technical Documentation
Please login or register for the Cooper Fire Community to download the technical documentation for this product.

The VoCALL 8 line exchange unit (CFCVX8) is a small wall mounted unit which can be distributed around the site and hidden from view in such places as rises, stairwells and cupboards.

Using this system greatly reduces the cabling requirement and equipment ‘on view ‘ in such key places as reception areas, making the system much more aesthetically pleasing to the customer as well reducing the cost of installation.

Features

  • Can control up to 8 independent monitored lines
  • Built in monitored 1A charger for 12V SLA batteries
  • 12 status LEDs
  • Dry contact for fault or “in-use” indication
  • Serial port for configuration or updates
  • Dual network ports which provide power for the master handsets
  • Full duplex system
  • Compact design

Benefits

  • LED indication, for effective & easy fault finding
  • Fault or ‘in-use’ relay, can be connected to a fire panel or BMS
  • Global configuration, upload information quickly via a PC using the serial port
  • Up to 32 distributed units on any network, no central exchange rack required

Physical

Height

296mm

Width

210mm

Depth

80mm

Weight

1600g

Material

Zintec, Texture powder coated RAL 7032

Power Supply

Voltage

230V ac ± 20%

Current

11mA

Battery

12V SLA 3.2Ah (Not supplied)

Charger

1A Controlled impedance

Monitoring

Open, short & high impedance cell

Processing

Architecture

AVR RISK

Clock

16MHz

Memory

4K Ram

20K EEProm

128K Flash

Monitoring

125mS Asynchronous watchdog Checksum on EEPROM & flash

 

CFVCX8