Products › VoCALL Master Handset

VoCALL Master Handset

This VoCALL Emergency Voice Communication System (EVCS) is designed to fully comply with BS5839 Pt9 2003 (abb. Pt9) for use as a fire telephone system, disabled refuge call system or as a combined system when both fire telephones and disabled refuge points are required. The standard states that where both systems are fitted to a building these should form a single system.

An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters during emergencies in high rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.

Download Technical Documentation
Please login or register for the Cooper Fire Community to download the technical documentation for this product.

The VoCALL master hand set can be either desk (CFVCM) or wall (CFVCWM) mounted.

Each system can have up to 8 master handsets which gives great flexibility to the larger installations allowing all calls to be monitored from various control points, as an example an installation may have security offices requiring a master handset, reception and numerous entrances that need to be monitored.

Features

  • Up to 8 masters per system
  • Controls up to 256 Lines (32 CFVCX8 exchanges)
  • Monitored handset
  • Large high contrast display (4 x 20 character)
  • 12 key quick dial keypad
  • Full duplex system
  • Directory dial function
  • Full system event log (fault & configuration)
  • 16 character unique name per line
  • Dual network ports
  • Remote powered

Benefits

  • Flexibility can be used as a fire telephone system, disabled refuge call system or as a combined system
  • Global configuration, whole site can be configured from the master handset.
  • Directory dialing, speed dial and conference calling
  • All hail function makes testing the system simple

Physical

Desk/Wall

Rack

Height

268mm

6u

Width

275mm

485mm

Depth

85mm

125mm

Weight

1490g

 

Materials

Base: Stainless steel brushed

Lid: Zintec, black powder coated

Sides: Aluminium, black powder coated

Power Supply

Source

Network Port x2

Voltage

11V to 18V dc

Current

88mA @ 12V

Processing

Architecture

AVR RISK

Clock

16MHz

Memory

4K Ram

20K EEProm

128K Flash

Monitoring

125mS Asynchronous watchdog

Checksum on EEPROM & flash

Network Cables

Grade

Enhanced

Cable (per Leg)

1 off four Pair (eg Draka 91-0245) or 2 off

four core 1mm CSA soft skin or 4 off

1 Pair MICC twisted

Distance (per leg)

500M soft skin types, 300M MICC

Monitoring

Data & phantom voltage

Indication & Controls

Fault LEDs

4 off yellow (General, Panel, Supply & Exchange)

Status LEDs

4 off green (Healthy, ac, dc & network)

LCD

High contrast blue/white LCD, four line twenty-character 5x8 pixel format

Keyboard

12 Key telephone style

Navigation

3 Keys (down/left, Accept, up/right)

Standards Compliance

EMC

EN55103-1, EN55103-2

Product Family

BS5839-pt9, BS5588-pt8

Options

Rack Mount Kit

Part VCRM

CFVCM

VoCALL Network Master handset - desk/wall mounting

CFVCWM

VoCALL Network Master handset - wall mounting