ULCS354 4 Way Sounder Controller Unit

An extensive range of interfaces are available to support the Cooper range of UL control panels, providing solutions for most design requirements.

The ULCS354 4 way sounder controller unit is a loop connected interface, which provides the facility to power and control 4 independent conventional sounder circuits.

Download Technical Documentation
Please login or register for the Cooper Fire Community to download the technical documentation for this product.

Download Data Sheet


An extensive range of interfaces are available to support the Cooper range of UL control panels, providing solutions for most design requirements.

The ULCS354 4 way sounder controller unit is a loop connected interface, which provides the facility to power and control 4 independent conventional sounder circuits. This greatly simplifies installation in applications where specialist sounders or beacons are required by avoiding the need to connect them directly to the analogue control panel.

The unit only uses a single address yet each circuit can be independently controlled according to the required cause and effect programming.

Features

  • Quick and simple to install
  • Avoids the need to wire conventional sounders back to the main panel
  • 4 separate sounder circuits (0.4 A)
  • All outputs are independently programmable
  • Battery backup via integral battery
  • Built in short circuit isolator class A style 7

Benefits

  • Plug and play - no hard addressing required
  • Increased system integrity. Self powered independency of SLC
  • No external short circuit isolator required
  • Beacon and strobe can be wired direct to the interface thereby saving time and cabling

Code

ULCS354

Description

 4 Way Sounder Controller Unit

Standards

UL864 9th edition

Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited

SLC Current

0.417 mA to 5.4 mA

Voltage

24 V

Line Impendance

50

Sounder 1, 2, 3, 4, Style Y, Class B, Supervised, Power Limited

Voltage

24 V

Sounder Load Per Channel

0.4 A (max)

Sounder Load Total

1.6 A (max)

End of Line Resistor

6.8 k

Line Impedance

16 (max)

Mains Supply

Voltage

120 V ac to 240 V ac

Current

0.1 A

Frequency

60 Hz

Environmental

Operating Temperature

0°C to 49°C

Humidity (Non Condensing)

0 to 93 %RH

Physical

Dimensions (H x W x D)

300mm x 300mm x 74mm

Weight

5.4kg

Ingress Protection

IP40

Battery Backup

2 x 12 V, 4 Ah, 0.1 derating factor

Standby

24 Hours + 30mins alarm

Charge Current

1 A (max)

Compatibility

Suitable for use with

Cooper analogue addressable fire systems

 

Code Description
ULCS354 4 Way Sounder Controller Unit