Products › ULCZMU352
ULCZMU352 Zone Monitor Unit
An extensive range of interfaces are available to support the Cooper range of UL control panels, providing solutions for most design requirements.
The ULCZMU352 zone monitor unit connects zones of suitable conventional detectors or pull stations.
An extensive range of interfaces are available to support the Cooper range of UL control panels, providing solutions for most design requirements.
The ULCZMU352 zone monitor unit connects zones of suitable conventional detectors or pull stations.
Features
- Quick and simple to install
- Monitors a zone of UL approved compatible conventional detectors
- Monitors a zone of UL approved compatible pull stations
- Only takes a single address
- Input monitored for open, short circuits and ground trouble
- Built in short circuit isolator
Benefits
- Plug and play - no hard addressing required
- Easy to expand a system using existing wiring
- No external short circuit isolator required
|
Code |
ULCZMU352 |
|---|---|
|
Description |
Zone Monitor Unit |
|
Standards |
UL864 9th edition |
|
Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited |
|
|
Load Current |
4.9 mA to 5.0 mA |
|
Supply Voltage |
24 V dc |
|
Detector Zone, Style C, Class B, Supervised, Power Limited |
|
|
Voltage |
21 V dc to 26 Vdc, 22.9 V dc (nom) |
|
Current (Alarm) |
17 mA to 40 mA |
|
Line Impendance |
2.5 Ω (max) |
|
End of Line Resistance |
6.6 kΩ |
|
Fire Input Trigger |
680 Ω |
|
|
UPCD-2W, UCPT-2W, UCHRI, UCHT any combination thereof |
|
Compatibility Identifier |
ULCV1 |
|
Callpoint Zone, Style C, Class B, Supervised, Power Limited |
|
|
Voltage (8.4 Vpp pulsed every 1 second) |
8.4 V |
|
Current |
1.2 mA |
|
Trigger Resistor |
680 Ω |
|
End of Line Resistor |
5.6 kΩ |
|
Line Impedance |
16 Ω |
|
Environmental |
|
|
Operating Temperature |
0°C to 49°C |
|
Humidity (Non Condensing) |
0 to 93 %RH |
|
Physical |
|
|
Dimensions (H x W x D) |
180mm x 129mm x 60mm |
|
Weight |
0.28kg |
|
Ingress Protection |
IP65 |
|
Compatibility |
|
|
Suitable for use with |
Cooper analogue addressable fire systems |
| Code | Description |
|---|---|
| ULCZMU352 | Zone Monitor Unit |
Cooper Fire Catalogue