Sorry, you need to enable JavaScript to visit this website.

ULCZMU352

ULCZMU352 Zone Monitor Unit

An extensive range of interfaces are available to support Eaton's range of UL control panels, providing solutions for most design requirements.

The ULCZMU352 zone monitor unit connects zones of suitable conventional detectors or pull stations.

Download Technical Documentation

Technical Documents

 

An extensive range of interfaces are available to support Eaton's range of UL control panels, providing solutions for most design requirements.

The ULCZMU352 zone monitor unit connects zones of suitable conventional detectors or pull stations.

Features

  • Quick and simple to install
  • Monitors a zone of UL approved compatible conventional detectors
  • Monitors a zone of UL approved compatible pull stations
  • Only takes a single address
  • Input monitored for open, short circuits and ground trouble
  • Built in short circuit isolator

Benefits

  • Plug and play - no hard addressing required
  • Easy to expand a system using existing wiring
  • No external short circuit isolator required

Code

ULCZMU352

Description

Zone Monitor Unit

Standards

UL864 9th edition

Signalling Line Circuit, Style 7, Class A, Supervised, Power Limited

Load Current

4.9 mA to 5.0 mA

Supply Voltage

24 V dc

Detector Zone, Style C, Class B, Supervised, Power Limited

Voltage

21 V dc to 26 Vdc, 22.9 V dc (nom)

Current (Alarm)

17 mA to 40 mA

Line Impendance

2.5 Ω (max)

End of Line Resistance

6.6 kΩ

Fire Input Trigger

680 Ω

 

UPCD-2W, UCPT-2W, UCHRI, UCHT

any combination thereof

Compatibility Identifier

ULCV1

Callpoint Zone, Style C, Class B, Supervised, Power Limited

Voltage (8.4 Vpp pulsed every 1 second)

8.4 V

Current

1.2 mA

Trigger Resistor

680 Ω

End of Line Resistor

5.6 kΩ

Line Impedance

16 Ω

Environmental

Operating Temperature

0°C to 49°C

Humidity (Non Condensing)

0 to 93 %RH

Physical

Dimensions (H x W x D)

180mm x 129mm x 60mm

Weight

0.28kg

Ingress Protection

IP65

Compatibility

Suitable for use with

Cooper analogue addressable fire systems

 

Code Description
ULCZMU352 Zone Monitor Unit

Unfortunately no online technical support is available for this product.
Please contact our Technical support team:

Technical Support
techsupport@cooperfire.com
Tel: 01302 303350
Fax: 01302 303332